Rigid Quik
Installation Instructions
- A hanger shall be required on each side of the coupling on all horizontal runs located within 18 in. of the center of the coupling
- The clamp assembly shall be torqued to a minimum of 60 inch pounds
- Couplings shall not be installed in fire rated construction that restricts the use of flammable materials through penetrations or plenums without additional fire-resistive protection.
- Couplings shall be installed in locations where the expected temperatures are between 0- 130 degrees F.